21
21
Figure 3.12: Text indicator
The boxes configured as a text indicator can be of several types: Binary, Integer (1 byte),
Percentage, Enumeration, Integer (2 bytes) and Float.
Binary: The 1-bit communication object "[Home x - Box y] Binary Indicator" is enabled,
and depending on the value received, "0" or "1", the text configured for the value "0" (Off
Text) or for the value "1" (On Text) will be displayed.
Integer (1 byte): The 1-byte communication object "[Home x - Box y] 1 byte Indicator" is
enabled and the state of this object, 0255, will be displayed. After downloading parameters
or a ‘reset device’ command the value displayed will be 0, until the object is updated.
Percentage: The 1-byte communication object "[Home x - Box y] Scaling Indicator" is
enabled and the state of this object, 0…255, will be converted to a percentage within the
range 0100 and displayed with a trailing ‘%’ symbol. After downloading parameters or a
‘reset device’ command the value displayed will be 0%, until the object is updated.
Enumeration: This option allows associating numerical values with texts. When
selecting it, the 1-byte object "[Home x - Box y] 1 byte Indicator" is enabled, and the following
options are shown:
# Enums: Depending on the chosen number, up to 6 value-text pair boxes will be
shown.
Value z: A value between 0 and 255 that if received by the object "[Home x - Box y]
1 byte Indicator" will cause the text specified in “Text z” to be displayed.
Text z: The text that will be displayed in the box when the object "[Home x - Box y] 1
byte Indicator" receives the value specified in "Value z".